How to Read a P-h Diagram (With a Live Interactive Example)

Two axes, one dome, four points. Here is how a pressure-enthalpy diagram works, worked through on a real R-410A cycle where every number comes from a live engine run — and where changing one input moves the loop in a way you can predict by eye.

September 2026 HVAC&R Engineering Guide 11 min read

Why the Cycle Lives on a P-h Diagram

A pressure-enthalpy diagram is a map of a refrigerant, and a refrigeration cycle is a closed loop drawn on that map. Each corner of the loop is a state your gauges and thermometers can find on a real machine. Read the map once and you stop memorising tables: compression ratio, compressor work, refrigerating effect and liquid-line subcooling all become distances on the same picture.

The reason it beats a temperature-entropy diagram for field and design work is what sits on the horizontal axis. Enthalpy is energy per kilogram, so any horizontal distance on the chart is an energy per kilogram directly: the work a compressor adds, the heat a condenser rejects, the cooling an evaporator delivers. No integration, no area under a curve — you measure across.

The one-sentence version: the vertical position of a point is the pressure it is at, the horizontal position is how much energy each kilogram of refrigerant is carrying, and the cycle is four points joined by four lines.

The Two Axes: Log Pressure and Enthalpy

Vertical axis: absolute pressure, logarithmic

Pressure is plotted on a log scale so that the suction side and the discharge side of a real cycle both stay readable on one chart: 933.2 kPa and 2,733.8 kPa are only one decade apart, but on a linear axis the low side would be squashed into the bottom few millimetres. Two conventions to keep straight:

Horizontal axis: specific enthalpy

Moving right means adding energy to each kilogram of refrigerant. That single idea explains the cycle:

The Dome, and the Three Regions It Creates

The dome is the two-phase boundary, and it splits the chart into three regions. For R-410A the dome closes at the top at 49.0 bar: that is the critical pressure, and above it there is no liquid-vapour distinction and no condensation at all.

The dome's two edges are the saturated liquid line and the saturated vapour line. On a single-component or near-azeotropic refrigerant they are sharp lines. On a blend with real glide they open into a bubble-point curve and a dew-point curve, and the gap between them is the glide you have to add into your superheat and subcooling measurements. That is the quantity that makes zeotropic blends harder to service, and it is visible on the chart before you ever touch a manifold.

The Four Points of Every Cycle

Every vapour-compression cycle is the same four states. Learn where each one sits and which measurement proves it is where you think it is.

PointWhat it isWhere it sitsWhat proves it
1Evaporator outlet / compressor suction Low-pressure isobar, just right of the saturated vapour line Suction superheat: suction temperature minus saturation temperature at suction pressure
2Compressor discharge Highest point of the loop, well inside the superheated region Discharge temperature against the compressor and oil limit, not just the pressure ratio
3Condenser outlet / liquid line High-pressure isobar, on or left of the saturated liquid line Subcooling: saturation temperature at liquid-line pressure minus liquid-line temperature
4Expansion valve outlet / evaporator inlet Back on the low-pressure isobar, inside the dome Quality: how much of the mixture has already flashed to vapour

Points 3 and 4 share the same enthalpy — that is the vertical line on the chart, and it is why you compare the evaporator outlet against point 4, never against point 3.

One Real Cycle, Every Number Measured

Here is the whole thing on a concrete cycle: R-410A, evaporating at 5 °C, condensing at 45 °C, 5 K of suction superheat, 2 K of liquid subcooling, compressor isentropic efficiency 70.0%, and a refrigerant mass flow of 0.10 kg/s. Every number below comes from refrigerant properties, not from a sketch.

200 250 300 350 400 450 500 700 1,000 1,500 2,000 3,000 5,000 critical pressure 4,901 kPa — the dome closes here Specific enthalpy h (kJ/kg) — energy each kilogram is carrying Absolute pressure P (kPa, log scale) subcooled liquid two-phase mixture superheated vapour saturated liquid line saturated vapour line 1 2 3 4 3′ 4′ 1→2 compressor: work added 2→3 condenser: heat rejected 3→4 expansion valve: h constant 4→1 evaporator: refrigerating effect 2 K subcooling (this run) 12 K subcooling (same suction and head) R-410A vapour-compression cycle on a pressure-enthalpy diagram

Figure 1 — The cycle as drawn by the engine. Numbers 1 to 4 are the four states; the dashed line is the same cycle with 12 K of subcooling instead of 2 K, which is the experiment in the next section. Change any input yourself in the interactive P-h diagram.

PointTemperaturePressureEnthalpyState
1 evaporator outlet10.0 °C933.2 kPa428.54 kJ/kg Superheated vapour, 5 K superheat
2 compressor discharge77.0 °C2,733.8 kPa471.65 kJ/kg Superheated vapour, 32.0 K above condensing temperature
3 condenser outlet43.0 °C2,733.8 kPa271.78 kJ/kg Subcooled liquid, 2 K subcooling
4 evaporator inlet4.93 °C933.2 kPa271.78 kJ/kg Two-phase, 29.9% vapour by mass

One engine run: R-410A, 5 °C evaporating, 45 °C condensing, 5 K superheat, 2 K subcooling, 70.0% isentropic efficiency, 0.10 kg/s. At this evaporating pressure the refrigerant enters at 207.5 kJ/kg as saturated liquid and leaves at 422.8 kJ/kg as saturated vapour — those two numbers are the endpoints the quality at point 4 is measured against.

Now read the four lines between the points, and the energy each one carries per kilogram of refrigerant:

ProcessOn the chartEnergy per kgPhysical meaning
1 → 2 compressionRises and moves right43.11 kJ/kg Compressor work in. This is the price of the 40 K lift, on every kilogram circulated.
2 → 3 condensationFlat at high pressure, moves left199.87 kJ/kg Heat rejected to the outdoor air. Always larger than the cooling delivered, because it also carries the compressor work.
3 → 4 expansionStraight down, no horizontal movement0 kJ/kg Pressure drops through the valve with enthalpy unchanged — the vertical line.
4 → 1 evaporationFlat at low pressure, moves right156.76 kJ/kg The cooling actually delivered: energy each kilogram absorbs from the space.

Consistent by definition: 156.76 + 43.11 = 199.87 kJ/kg. If the numbers you read off a chart do not add up this way, you have misread a point.

The performance that falls out of the same run: 4.31 kW of compressor power, 15.68 kW of cooling, COP 3.64, and 19.99 kW rejected at the condenser. The theoretical maximum (Carnot) for a 40.0 K lift is 5.19, so this cycle is running at 70.0% of that limit — real equipment behaviour, and the gap worth comparing against a machine you actually own. The COP calculator and the COP efficiency guide go deeper on that comparison.

Move One Input: the Subcooling Experiment

A P-h diagram earns its keep when you move one input and watch the loop change. Keep everything from the run above and change only the subcooling, from 2 K to 12 K.

Points 1 and 2 do not move at all. Suction state, discharge pressure and compressor work are identical, because nothing about the evaporator or the compressor changed. What moves is point 3: liquid now leaves the condenser at 33.0 °C instead of 43.0 °C, so it sits further left at 253.08 kJ/kg instead of 271.78 kJ/kg, and the vertical expansion line drags point 4 with it, to 253.08 kJ/kg.

Quantity2 K subcooling12 K subcoolingChange
Liquid-line temperature (point 3)43.0 °C33.0 °C−10 K
Enthalpy at the valve outlet (point 4)271.78 kJ/kg253.08 kJ/kglower: colder mixture
Flash gas at the evaporator inlet29.9% vapour21.2% vapour29.1% less flash gas
Refrigerating effect156.76 kJ/kg175.46 kJ/kg+11.9%
Cooling capacity at the same power15.68 kW17.55 kW+11.9%
COP3.644.07+11.9%

Read that again, because it is the most useful habit the diagram teaches: at the same compressor power, 29.1% of the flash gas at the evaporator inlet is gone and the system moves 11.9% more heat. Point 4 starts further left inside the dome, so every kilogram of refrigerant can absorb more heat before it reaches point 1.

Do not read this as free efficiency. The gain is real, but it comes from somewhere. If the condenser circuit physically delivers that subcooling, you have earned it. If it appears because the system is overcharged, the extra liquid buys you a flooded compressor or a slugged valve later. If you manufacture it with a suction-line heat exchanger, you are trading it against suction superheat, which raises discharge temperature. The diagram shows the trade; it cannot tell you which side you are on — the gauges do.

Run the same experiment in the live tools with your own pressures: the superheat & subcooling calculator for the field measurements, the superheat and subcooling guide for the targets, and the P-h diagram tool for the picture your numbers make.

Five Misreadings That Cost You a Diagnosis

  1. Plotting gauge pressure instead of absolute. Every P-h chart is absolute pressure, so a manifold reading of 9.33 bar on the low side is plotted at about 9.33 bar absolute plus the atmospheric offset. One bar of error moves every state on the chart.
  2. Using one saturation temperature for a blend. On a zeotropic blend the bubble point and the dew point differ and the dome is a band, not a pair of crisp lines. Compare the liquid line to the bubble point and suction to the dew point, or superheat and subcooling both read wrong by the glide.
  3. Measuring temperature and pressure at different places. Suction superheat is a point-1 number only if both values come from the same point. A pressure tap at the compressor with a temperature at the evaporator outlet puts suction-line pressure drop silently inside your superheat.
  4. Drawing the compression line straight up. A real compressor is not isentropic. At 70.0% efficiency the discharge lands at 77.0 °C instead of the ideal-compression temperature, further right on the chart because friction work is real enthalpy. Plot an isentropic line and you cannot explain a hot-running compressor.
  5. Taking the refrigerating effect from the wrong point. Cooling per kilogram is point 1 minus point 4, not point 1 minus point 3. Using the liquid-line enthalpy ignores the flash gas that already formed in the valve and overstates capacity — here it would inflate the number by about 29.9%.

The 60-Second Read

On a real system, six checks in this order find most of what is wrong, and each one is a glance on the chart:

  1. Is the loop closed? Four points in the right order. A missing measurement is a guessed point, and a guessed point hides the fault.
  2. Compression ratio from the two pressures: 2.93:1 at a 40.0 K lift here. A rising ratio at the same load usually means a condenser problem, not a compressor problem.
  3. Suction superheat. Small but positive. Zero means liquid is reaching the compressor; a large number with poor capacity means a starved evaporator.
  4. Liquid-line subcooling. Positive under a TXV. Near zero or negative points at charge, condenser air flow, or a restriction before the valve.
  5. Evaporator inlet quality. Inside the dome, and not so far right that most of the refrigerant arrives as flash gas — the number the P-h diagram tool prints for you.
  6. Discharge temperature against the compressor limit: 77.0 °C here at 70.0% efficiency. If the measured value is far higher, look at suction superheat and pressure ratio before blaming the compressor.

Draw Your Own Cycle in Seconds

Set evaporating and condensing temperature, superheat, subcooling and compressor efficiency and the interactive P-h diagram redraws the dome, the loop and all four state points, with every number labelled. Free, browser-based, no install.

Open the Interactive P-h Diagram →

Also useful: refrigerant comparison calculator  ·  R-410A property page  ·  superheat & subcooling

Save Your Cycles, Not Just Look at Them

A free account stores your systems, compares refrigerants on the cycle you actually run, and exports the numbers to a calculation sheet. Free tier, 20 calculations a month, no card.

Create a Free Account →
See Plans — Pro $29/mo for the first 100

Questions Engineers Ask

What is a P-h diagram used for?

To see a refrigeration cycle as state points and energy distances: compression ratio, compressor work, heat rejection, refrigerating effect, liquid subcooling and evaporator-inlet flash gas on one chart — for design work, and for diagnosing a system that is not performing to design.

How do I find the four state points?

Measure two independent properties per point. Suction and discharge pressures set the vertical positions; superheat, subcooling and the constant-enthalpy expansion rule set the horizontal ones. Points 3 and 4 always share an enthalpy, and points 1 and 3 never do.

Why is the pressure axis logarithmic?

So the low side and the high side of a real cycle both stay readable. On a linear axis a suction pressure of 933.2 kPa collapses against a discharge pressure of 2,733.8 kPa and the evaporator region cannot be resolved at all.

What does the horizontal distance between points mean?

Energy per kilogram of refrigerant. Point 1 to point 2 is the compressor work, point 4 to point 1 is the refrigerating effect, and their sum is the heat the condenser rejects between points 2 and 3.

Can I read a P-h diagram without refrigerant property tables?

Not accurately by hand — the dome and the enthalpies come from an equation of state, and interpolating them manually is where errors creep in. Use the interactive P-h diagram or the refrigerant comparison calculator, which compute the properties live, then read the shape of the cycle exactly as you would on paper.

Related reading: R-454B vs R-410A transition guide · all engineering guides · the live cycle demo.