Refrigerant Pressure-Temperature Chart

Every field technician keeps a P-T chart in the truck: knowing saturation pressure tells you the evaporating temperature on gauges, and vice versa. The table below is computed from real thermodynamic property data (CoolProp) for the six most common service refrigerants.

Use it for charging checks, TXV adjustment, and diagnosis. Need full cycle state points? The superheat & subcooling calculator above builds on the same data.

Temp °CR134aR410AR32R404AR290 (propane)R744 (CO2)
-40°C51.2 kPa174.8 kPa177.4 kPa131 kPa111.1 kPa1004.5 kPa
-35°C66.1 kPa218.1 kPa221.4 kPa163.6 kPa137.2 kPa1202.4 kPa
-30°C84.4 kPa269.3 kPa273.4 kPa202.2 kPa167.8 kPa1427.8 kPa
-25°C106.4 kPa329.4 kPa334.6 kPa247.5 kPa203.4 kPa1682.7 kPa
-20°C132.7 kPa399.3 kPa405.8 kPa300.2 kPa244.5 kPa1969.6 kPa
-15°C163.9 kPa480 kPa488.1 kPa361 kPa291.6 kPa2290.8 kPa
-10°C200.6 kPa572.7 kPa582.6 kPa430.7 kPa345.3 kPa2648.7 kPa
-5°C243.3 kPa678.3 kPa690.6 kPa510.2 kPa406 kPa3045.9 kPa
0°C292.8 kPa798.1 kPa813.1 kPa600.3 kPa474.5 kPa3485.1 kPa
5°C349.7 kPa933.2 kPa951.4 kPa701.8 kPa551.1 kPa3969.5 kPa
10°C414.6 kPa1084.8 kPa1106.9 kPa815.7 kPa636.6 kPa4502.2 kPa
15°C488.4 kPa1254.3 kPa1280.8 kPa942.9 kPa731.5 kPa5087.1 kPa
20°C571.7 kPa1442.9 kPa1474.6 kPa1084.4 kPa836.5 kPa5729.1 kPa
25°C665.4 kPa1652.1 kPa1689.6 kPa1241.2 kPa952.1 kPa6434.2 kPa
30°C770.2 kPa1883.4 kPa1927.5 kPa1414.5 kPa1079 kPa7213.7 kPa
35°C887 kPa2138.3 kPa2189.8 kPa1605.3 kPa1217.9 kPa—
40°C1016.6 kPa2418.6 kPa2478.3 kPa1814.9 kPa1369.4 kPa—
45°C1159.9 kPa2726.1 kPa2794.8 kPa2044.7 kPa1534.3 kPa—
50°C1317.9 kPa3063 kPa3141.2 kPa2296.1 kPa1713.3 kPa—
55°C1491.5 kPa3431.6 kPa3519.9 kPa2570.9 kPa1907.2 kPa—
60°C1681.8 kPa3834.8 kPa3933.2 kPa2871.2 kPa2116.8 kPa—
65°C1889.8 kPa4276.3 kPa4384.3 kPa3200 kPa2343 kPa—
70°C2116.8 kPa4761.7 kPa4876.8 kPa3563.3 kPa2586.8 kPa—

Saturated vapor line, absolute pressure (kPa). Generated from real CoolProp property data. R744 (CO2) has no saturation values above its critical temperature (31.1°C) — it operates transcritically there.

Frequently asked questions

How do I read a P-T chart?

Find your refrigerant column and read across: the pressure (kPa) at which it boils/condenses at each temperature. At sea level, R410A saturated at 45°C reads ~2,730 kPa; R134a at the same temperature ~1,160 kPa.

Why is R744 (CO2) pressure so much higher?

CO2's critical temperature is 31°C — in warm ambient it operates transcritically above 7,400 kPa. That's why CO2 systems use different fittings and safety standards.

Are these values gauge or absolute pressure?

Absolute pressure in kPa. Subtract ~101.3 kPa (14.7 psi) for gauge readings at sea level.